Skip to main content

Commercial Solar Photovoltaic (PV) Checklist

Plans

  1. Site Plan
    • Show north arrow
    • Property lines and dimensions (size and shape of parcel); include easements
    • Locations, dimensions and height of all existing and proposed buildings and structures. Include dimensions from each other and from all property lines.
    • Existing and proposed driveways including width, curbs, sidewalks, and streets.
    • Indicate placement and species of required street trees.
    • Indicate center line of street(s), label street names and note as public or private.
    • Location and height of walls and fences; note construction material(s).
    • Show fire lanes, hydrants, and building entrances.
  2. Roof Plan (layout plan for ground-mounted)
    • Location and dimensions of solar array with dimensioned pathways and clearances
    • Existing rooftop equipment, vents, and other roof penetrations
    • Location, size, and type of roof access (stairs, permanent ladder, etc.)
  3. Electrical Plans
    • If net metering, then Production Meter must be shown on the one-line drawing
    • Rapid Shutdown and Emergency Disconnects [IFC 1205.4]
      • Identification of rapid shutdown device(s) and control location
      • Notation of UL 3741 or UL 1741 listing for rapid shutdown systems
      • Description of shutdown activation method and compliance with NEC 690.12
    • System Labeling and Signage
      • Label locations on plans and one-line diagram, and in the field [NEC Article 690]
        • DC disconnects
        • Combiner boxes
        • Inverters and conduit
        • Rapid shutdown initiation devices [IFC 1205.4.1, 1205.4.3]
      • Warning signs on or near equipment: “WARNING—ELECTRIC SHOCK HAZARD—DO NOT TOUCH TERMINALS”
    • Hazard Mitigation
      • Arc-fault and ground-fault protection documentation
      • Fire-resistance rating of roof penetrations and sealing materials
      • Battery system fire safety plan (if applicable):
        • Ventilation provisions
        • Separation from combustible materials
        • Fire-rated enclosure
  4. Structural Plans (when applicable) and attachment details

Documents

  1. Signed and Dated Commercial, Multi-Family & Industrial (CMI) Application Form (PDF)
  2. Manufacturer’s Equipment Specifications (spec sheets)
    • PV modules -UL 61730
    • Inverters – UL 1741
    • Racking/mounting system – UL 2703
  3. Structural Calculations (when applicable)

Resources